Size Is Not Important When It Comes To Putting Out A Fire

Fireworks manufacture a unique fire suppression system that uses atomised high pressure water to extinguish a fire by rapid cooling at the flame front. The water droplets dramatically reduce the temperature in the room and also absorb smoke particles. Their systems are already installed in more than 100 prisons in the UK where they are installed primarily to tackle cell fires.  The principle, however, can be used in much larger situations.

Custodial Review spoke to Derek Killaspy to find out more.
CR    Much of the equipment you have fitted into prisons has been concerned with extinguishing cell fires or on landings which tend to be small blazes in a confined areas.  What I would like to discuss is the application of your technology in areas where larger blazes can occur, such as a kitchen.
DK    The worst fire that can happen in a kitchen is a deep fat fryer blaze. Hydramist is ideal for these risks because of how it puts out fires in hot oil. The system works by using the heat of the fire to convert the atomised water into steam. This both rapidly reduces the temperature of the oil and creates an oxygen free area at the flame front and therefore quickly and efficiently extinguishes the fire..  Because the hot oil is quickly cooled re-ignition of the fire is prevented.
CR    Usual advice is never put water on a fat or oil fire, so why would you spray water onto an oil fire?
DK    The reason for the advice is that water is heavier than oil and it expands over 1100 times when it turns from water into steam. Oil usually cooks at 180 degrees and has a huge amount of latent heat due to the volume of oil in the fryer. so water poured into hot oil sinks under the surface then expands so quickly it’s almost an explosion. This causes the oil so be showered over a large area, usually including the person who poured the water into the oil.
What the Hydramist system does is to spray atomised water onto the flame front and heat above the oil. The water droplets do not sink under the surface as they are constantly converted to steam above the oil until the temperature reduces to below 100 degrees C. So the atomised water never gets under the surface of the oil whilst a danger of it turning to steam exists. Therefore it cannot cause an explosion.
The reason the system works so effectively is because the atomised water is turned to steam at the flame front and so removes heat from the fire and oil, it then condenses and can fall back onto the blaze, repeating the cooling process.
The atomised water never gets under the surface of the oil whilst a danger of it turning to steam exist, therefore it cannot cause a ‘fat explosion’.
CR    Is there a limit to the size of fryer you can protect with this system? I ask because the huge amount of heat stored in large amounts of oil would take some time to cool.
DK    We are presently protecting a whole range of commercial fryers of the type you would see in fast food outlets and restaurants, we are also protecting fryers in factories that are several metres long, and contain several tons of oil. So the answer to your question is that there is no limit to the size of fire the system can extinguish.
CR    The amount of heat stored in hot oil must limit the speed at which fires are extinguished, as there is a lot of heat to vaporise the water droplets into steam. So how long does it take to put out an average commercial chip fryer?
DK    Oil that has caught fire is probably at a temperature of 240 degrees C and with one nozzle working it takes about 2-4 seconds to extinguish the flames and less than 1 litre of water, and about 2 minutes until the oil temperature is down bellow its flash point.
CR    The nozzle; is this on a hand held device similar to the cell fighting equipment you supply or is it a pre installed and plumbed unit?
DK    It’s preinstalled and plumbed because the philosophy behind our system is that the person who is using the fryer probably isn’t a trained fire-fighter.  We do not recommend that anything hand held, like a fire blanket or an extinguisher, is used as the person has to get close to the fire and risk possible injury. Our system is completely automatic, though it will also have a manual start placed some distance away. In all the testing we have done in conjunction with (Building Research Establishment , BRE) we have proven that our automatic system is quicker and more efficient than any other system for this risk.
CR    Where is this nozzle positioned and how is it triggered? Are there any warning signs?
DK    It’s approximately 1.3 meters above the fryer, so it’s out of the way of the operator and cannot cause injury. There is a heat sensitive bulb in the nozzle and when it reaches a pre set temperature the bulb breaks and this triggers a flow of water and the pump to activate. The temperature at which the bulb breaks can be varied, but for a typical fat fryer protection system it will operate at 93 degrees C.
CR    Playing devils advocate now. You have a nozzle 1.3 meters above a large pan of 180 degree oil. What happens if it goes wrong and squirts a stream of cold water straight into the fat right in front of the operator?

DK    This cannot happen. When the pump isn’t activated the system only has water in it at tap pressure; this is typically 1 to 4 bar. The nozzle will not open until the pressure of the water reaches 20 bar. Tap pressure will never reach this high. When the bulb breaks there will be a 30 millisecond burst of water at tap pressure, before the pump kicks in and boosts the pressure to a sufficient level to atomise the water. In tests we have found that the high pressure misted water reaches the hot oil before the initial low pressure dribble caused by the bulb breaking.
CR    What happens if the pump fails?
DK    You will get a light fine spray of mist at a pressure of 1-4 bar. This will cause the oil to pop and spit a bit but there is not sufficient water to cause it to erupt.
CR    Is it recommended to install this sort of suppression system above any other type of kitchen equipment?
DK    it can be installed at any location in a kitchen, however the standard LPS 1223 regulations for fat fryers only apply to them or similar equipment.
CR    What are the alternatives to the type of system you supply?
DK    Chemical dispensers or foam, both of which leave a residue of chemicals over the area sprayed. They do work, and almost as quickly as the Hydramist system, but they form a hard cap on the oil so it takes much longer for the oil to cool down and it’s a long time before any clean up can take place. Kitchens are then shut for the full duration of the clean up process. With our system all there is to clean up is a small amount of water, typically a kitchen will be back in use 30 minutes after an incident with the Hydramist system.  It can take several hours to reinstate the kitchen after an incident with a chemical fire suppression system.
CR    What are the implications for false activation for suppression systems?
DK    False activation is very unlikely in either case, however if a chemical system goes off then there is an extensive clean up procedure to go through. If a Hydramist system goes off it can be quickly cleaned up with a cloth and mop. The water in the oil will evaporate and the oil can be used again.   The chemical system will contaminate the oil requiring a complete oil change and clean.
CR    Cost comparisons on installation, what is cheaper, yours or the chemical system?
DK    On a one fryer system we are slightly more expensive, with 2 or 3 nozzles we are cheaper as we only need one pump. Generally the larger the risk the more chemical required, we always use the same size pump and are therefore more competitive in our design and costing, add to this the savings from any clean up after a chemical system has been used and our system comes out on top.  Additionally our maintenance costs are lower as we don’t need to re-fill with expensive chemicals.
We should also mention our environmental credentials; we use only water to fight the fire with no chemicals or additives.  Our system presents no risk to people or our environment.
CR    Thank you for talking to the Review.
Fireworks Fire Protection will be exhibiting at the ‘Criminal Justice Management 2011’ event on 29th September that will take place at the QEII Conference Centre, London.
For further information on the Watermist fire extinguishing systems please contact Derek Killaspy
at Fireworks Fire Protection on
01953 458 420 or 0800 977 7834 or visit www.fireworks-ltd.com,
email derek@fireworks-ltd.com

     
   
   
 
  Link to this article:
(Copy and paste the following code to your web page.)
 
 

The Custodial Review - More Articles
 
 

 


     
 

Review Magazines. All rights reserved    Tel: 01234 348878 Fax: 01223 790191       Email: sales@pirnet.co.uk             Sitemap

 
  wirelessivityFreeview LCD Televisions